- New
- Out Of Stock - info [email protected]
CM-6
CM-6 MACURCO - AERIONICS Carbon Monoxide Detector Controller and Transducer
• Power: 3 W (max) from 12 to 24 VAC or 12 to 32 VDC
• Current 24 VDC: 75 mA in alarm 50 mA fan relay on and 23 mA stand by
• Shipping Weight: 1 pound (0.45 kg)
• Size: 4 1/2 x 4 x 2 1/8 in. (11.4 X 10.2 X 5.4 cm)
• Color: Dark gray • Connections: plugs/terminals
• Mounting Box: (not included) 4x4 electrical
• Fan Relay: 5 A 240 VAC pilot duty SPDT latching or non-latching
• Fan Relay Actuation: selectable at “dIS” (disabled) 15 ppm 25 ppm 35 ppm (default) 50 ppm or 100 ppm
• Fan Delay Settings: 0 1 3 (default) 5 and 10 minutes
• Fan Relay Minimum Runtime Settings: 0 (default) 3 5 10 or 15 minutes
• Alarm Relay: 0.5A 120 V 60 VA
• Alarm Relay Actuation: selectable N.O. default or N.C.
• Alarm Relay Settings: dIS 50 ppm 100 ppm 150 ppm and 200 ppm (default)
• Current Loop: 4-20 mA for 0-200 ppm
• Operating Environment: 0°F to 125° F (-18°C to 52°C) 10 to 90% RH non-condensing
Carbon Monoxide Detector and Controller
The MACURCO CM6 is a low voltage detector controller and transducer with a built-in double relay selectable output selectable output from 4-20 mA buzzer and digital screen is an electronic detection system used to measure the concentration of CO and provide feedback and control the automatic fan/extractor to reduce the concentration of CO in parking lots maintenance areas and other commercial applications.
Features:
- UL list
- Mounting standard electrical box 4 "x 4"
- Factory calibrated
- Activation of the selectable fan relay in 15 25 35 (by default) 50 or 100 ppm of CO
- Capable of showing concentrations of CO in the range of 0 to 200 ppm
- Alarm relay of NA or NC 0.5 A
-Fan relay: SPDT 5 A
- Design of supervised system: a problem in the detector will activate the fan and alarm
- Dimensions: 114 X 102 X 54 mm
2023-09-27 00:55:26
Page: 8
Reviews
No customer reviews for the moment.