TSJ-6A TRANSTECTOR Data Surge Protector SPD TSJ Indoor Ports RJ11 SASD (1100-592-1)
The TSJ 6A surge suppressor is a high-current solid-state device designed to protect equipment from transient over-voltages on telephone lines with RJ-11 connectors using pins 3 and 4. It performs this function by limiting the magnitude of transient over-voltages that are present on the pair relative to each other and from each relative to ground. Continuous bipolar bi-directional non-interrupting protection is provided. The TSJ 6A utilizes silicon junction avalanche suppressor diodes as its sole suppression technology and automatically resets after each suppression function with no degradation of protection capabilities.
The TSJ 6A attaches in series with the load to be protected. It is also equipped with a 12” wire for the purpose of attaching the device to the system GND (required for proper suppression).
ELECTRICAL SERVICE:
Maximum Continuous Operating Voltage:………………………………………..160V Peak
Connector Type:…………………………………………………………………………..RJ-11
Protected RJ-11 Pins:………………………………..Pins 3-4; Pin 3 to GND; Pin 4 to GND
Pass-Thru RJ-11 Pins:…………………………………………………………………Pins 2 5
ELECTRICAL PERFORMANCE:
Turn-on Voltage…………………………………………………………….Vbr 192V 5mA
Maximum Voltage Protection Level (10/1000µs)………………………………264Vp45A
Maximum Voltage Protection Level (8/20µs)………………………………….344Vp400A
Response Time (Max)……………………………………………………………………...<5ns
Series Impedance……………………………………………………………………..33 Ohms
Max. Leakage Current………………………………………………………………………5µA
ENVIRONMENTAL:
Temperature (Operating and Storage)…………………………………………-30º to 65ºC
Relative Humidity……………………………………………………………………………90%
MECHANICAL:
Dimensions……………………………………………………2.2” 5.6X2.2”5.6x0.89”2.26
Weight…………………………………………………………………………0.15 lb. 0.068kg
UL Material Flame Rating………………………………………………………………..94-V0
Installation Connections: One (1) RJ-11 female receptacle (input from Line) one (1) RJ-
11 plug (output to Equipment) and one green 20 AWG GND wire (to be connected to
same system GND as protected equipment).
Note: Trim ground lead as short as possible for optimum suppression.